How Often Should SF6 Relay be Checked?

In the preventive test regulations of electrical equipment, SF6 relay, the verification cycle is a key issue. According to the DL/T596-1996 Regulations for Preventive Testing of Electrical Equipment implemented by the Ministry of Electric Power on January 1,1997st, the SF6 relay should be verified regularly with a cycle of 2 years. In addition, it is recommended to perform a verification test once a year to ensure the stability and reliability of the equipment.


Using the Inflation Process of SF6 Relay for Verification


The inflation process of SF6 relay is used to identify some issues:


  • Temperature has a significant impact, making it difficult to ensure accuracy.


  • Using the reading on the SF6 gas cylinder, accuracy is poor and cannot be guaranteed.


  • When actually used in the pressure reduction process, using the inflation process for verifying the density relay does not conform to the actual application scenario, affecting accuracy.


Using the Gas Recovery Process of SF6 Relay for Verification


Using the gas recovery process of SF6 equipment for verifying the density relay, the following problems exist:


  • Similar to the inflation process, there are accuracy issues.


  • A specific SF6 gas recovery device is required, which is inconvenient to operate.


Verification Precautions for SF6 Relay


To ensure the safety of verification work, the following are the precautions that need to be taken when verifying the SF6 relay:


  • Check the gas circuit structure of the SF6 relay to ensure gas circuit isolation.


  • Process the work permit to ensure orderly work.


  • Close the isolation valves and disconnect the check valve to ensure the accuracy of verification.


  • Perform alarm and interlock circuit action checks to ensure system safety.


  • After verification, use leak detectors to check for leaks and ensure sealing.


  • The verification device should be dedicated to the SF6 relay and should not be used for other pressure instruments.


  • Temperature should be balanced over an appropriate period of time.


  • Follow the verification process to ensure the entire process is sealed and safe.


  • The valve of the verification port should be closed first, and the valve connected to the relay should be opened later to ensure safe operation.


  • Record relevant information of density relays of different models and manufacturers, and establish a database.


The accuracy and reliability of the SF6 relay are directly related to the safe operation of electrical equipment. Through reasonable periodic verification and compliance with precautions, the SF6 relay can function reliably under various conditions, enhancing the safety and stability of the equipment.

Related Article for Reference

What Are the Differences and Functions of the Pressure Gauge and Relay Used in SF6 Circuit Breakers?
SF6 circuit breakers play a critical role in electrical equipment, and pressure gauges and density relays are essential components that ensure the proper operation of the equipment. In this article, w...
Fri 01 2024
Function and Principle of SF6 Gas Density Meter
SF6 Gas Density Meter FunctionDensity refers to the mass per unit volume of a specific substance under specific conditions.SF6 gas in circuit breakers is sealed in a fixed container. It has a certain ...
Mon 03 2024
Judgment of Test Methods and Test Results of SF6 Gas Density Relay
SF6 relay is an important protection and control element in the power system. If the circuit breaker fails, it will cause great economic losses. To ensure the reliability of the circuit breaker operat...
Sat 10 2022
Lanso Instruments INC.
233 W 1st St #210, North Vancouver, Canada
info@lansoinstruments.com
233 W 1st St #210, North Vancouver, Canada
info@lansoinstruments.com