Email
info@lansoinstruments.com
SF6 Gas Insulated RMU
SF6 Gas Insulated Switchgear
Bimetal temperature compensation ensures higher measurement accuracy.
Suitable for indoor or outdoor installation
AISI 304 hermetically sealed stainless steel case
Gas connection tubes are made of AISI 316 stainless steel
The on-screen display value and output signals are independent of the impact of external environment, such as altitude
Case diameter: | 64mm |
Scale range: | 1 to 2bar abs |
Accuracy: | ±1.5%FS(+20±1℃),±2.5%FS(-20℃~+60℃)(gas phase) |
Degree of protection: | IP65 |
Ambient conditions: | -20°C to +60°C,relative humidity ≤ 95%RH |
Leakage rate: | ≤1 × 10-9 Pa·m3/s (Helium leakage inspection) |
Process connection: | M24 × 1.5 (customizable) |
Installation method: | Radial or Axial |
Watch glass: | Laminated safety glass |
Impact rating: | 30g |
Weight: | ≈0.2kg |
Pressure element: | Bourdon tubes |
Process connection: customizable
Measuring Medium: SF6, Air, N2, SF6 + N2 and other gases
Suitable for High-altitude environment
Wider temperature range: -40℃ to +60℃
Optional measurement accuracy:±1.0%FS(+20±1℃),±2.5%FS(-20℃~+60℃)(gas phase)